| Date | Port | Detained | Deficiencies |
|---|---|---|---|
| 13 Feb 2026 | Boston | No | 2System: 07 - Fire Safety Sub-System: N/A - No Subsystem Component: 07110 - Fire Fighting Equipment And Appliances Cause: Improper/Lack Of Maintenance Action: 10 - Deficiency Rectified Action Code: C - To The Satisfaction Of The Coast Guard Description Of Deficiency: Monthly Inspections Should Be Carried Out To Ensure That All Fireman’S Outfits, Fire Extinguishers, Fire Hydrants, Hose And Nozzles Are In Place, Properly Arranged, And Are In Proper Condition. PSCO Observed CO2 Extinguisher #41 Had Not Been Inspected In Over 2 Months. Code 07110, 74 SOLAS (09) II-2/14.2.2.1; MSC/Circ.850, 10c Due Date: N/A Deficiency Resolved? Yes Resolved Date: 2/13/2026 12:00:00 AM Resolution Description: Ship'S Crew Performed Required Monthly Inspection To The Satisfaction Of Attending PSCO. System: 07 - Fire Safety Sub-System: N/A - No Subsystem Component: 07105 - Fire Doors/Openings In Fire-Resisting Divisions Cause: Improper/Lack Of Maintenance Action: 10 - Deficiency Rectified Action Code: C - To The Satisfaction Of The Coast Guard Description Of Deficiency: The Purpose Of This Regulation Is To Contain A Fire In Space Or Origin. For This Purpose, The Following Functional Requirements Shall Be Met: The Fire Integrity Of The Divisions Shall Be Maintained At Openings And Penetrations. PSCO Observed The Following “A” Doors Would Not Latch: 108, 134 And A Hole In The “A” Boundary Bulkhead Leading To Steering Gear Room. Code 07105, 74 SOLAS (09) II-2/9.1.3, 10c Due Date: N/A Deficiency Resolved? Yes Resolved Date: 2/13/2026 12:00:00 AM Resolution Description: Ship'S Crew Rectified The Deficiency To The Satisfaction Of Attending PSCO. |